280B-PL Series
Rate-of-Rise and Fixed Temperature Heat Detectors
Description
*NOTE: Maximum detector coverage has been determined by UL to provide detection time equal to sprinkler devices spaced at 10 ft (3.05m) intervals on a smooth ceiling 15 feet 9 inches (4.8m) high. Higher ceilings may adversely affect detection time. Earlier detection may be obtained by reducing the spacing between detectors. (See NFPA 72, Chapter 5) Detector twists and locks onto mounting plate. Mounting plate may be surface mounted or mounted onto any 3 1/4" (83mm) or 4" (102mm) octagon box. |
Link to this product
|
Catalog Numbers
| Catalog Number
|
Description
|
|||||||
Specifications
Approvals
Agency ApprovalsUL Listed FM Approved CSFM Listed
Specifications
- Single circuit normally open contact rated at 3 amps at 6 to 125V AC; 1.0 amps at 6 to 28V DC, 0.3 amps at 125V DC, and .01 amps at 250V DC
- Maximum coverage 2,500 sq. ft. (232.25 sq. m)
- UL spacing: 50 ft (15.24m)
- FM spacing: 30 ft (9.14m)
- Color - white
| Cat. No. | Description | Rate-of-Rise Rating | UL Temp. Rating °F | UL Max. Ambient Ceiling Temp. Rating °F |
| 281B-PL | ROR & Fixed | 15F/min. | 135 | 100 |
| 282B-PL | ROR & Fixed | 15F/min. | 194 | 150 |
| 283B-PL | Fixed | -- | 135 | 100 |
| 284B-PL | Fixed | -- | 194 | 150 |
Manuals
Catalog Pages
Installation Instructions
Technical Bulletins
Installation Instructions
Technical Bulletins
- Fire Alarm Design Criteria
- Wiring Guide Tech Bulletin
Fire Alarm Signaling Systems Wiring Practices Manual